CNHONOR · REFRIGERATION

Ammonia refrigeration unit

PRECISION ENGINEERING · COLD-CHAIN EQUIPMENT

Ammonia refrigeration unit

An open-drive screw compressor unit with adjustable capacity, economizer options and centralized control connectivity.

Discuss this product ↗
Product overview
Features
  • Safety and reliability

    Designed for high safety standards, with configurations based on GB/T 19410 and applicable European industrial product requirements and certifications.

  • Low energy consumption

    Equipped with a Japanese Mayekawa SRV open-drive screw compressor. An adjustable internal volume-ratio slide valve supports efficient operation across different conditions.

  • High efficiency

    The Mayekawa SRV open-drive screw compressor uses an adjustable internal volume ratio. An economizer supplies intermediate-stage vapor injection to increase liquid subcooling and improve system COP.

  • Control system

    A stable, easy-to-use controller provides an interactive interface and real-time monitoring of pressure, temperature, operating time and capacity. Connection to a central control system enables remote monitoring, operation and alarms for unattended operation.

Model designation
Control options
1. Standard and premium configurations are available.
2. Standard configurations offer manual or automatic control.
Applications
1. Food processing: dumplings, rice balls, noodles, fish balls and related systems.
2. Seafood processing: fish, shrimp and related systems.
3. Meat processing: poultry, pork, beef and lamb processing systems.
4. Cold-chain logistics: cold stores and fresh produce storage of different sizes.
5. Chemical and pharmaceutical industries: process temperature control, pharmaceutical freeze-drying and storage.

160 Series single-stage compressor unit specifications
Item Unit 160 Series
Refrigerant type R717
Model 160S 160M 160L
Theoretical displacement m³/h 415 519 622
Capacity control range Stepless adjustment: 10–100%
Cooling capacity High-temperature conditions Kw 494 618 740
Medium-temperature conditions Kw 272 341 409
Low-temperature conditions / with economizer Kw 84/98 105/123 126/147
Motor High-temperature conditions Kw 90 110 123
Medium-temperature conditions Kw 90 110 123
Low-temperature conditions / with economizer Kw 75 90 110
Electrical supply 380V/50HZ/3N
Rated speed r/min 2960
Direction of rotation Clockwise (viewed from the motor shaft end)
Refrigeration oil Grade 46#
Standard GB/T 16630, Refrigeration Oils
Charge quantity Kg 200 200 250
Notes:
1. High-temperature conditions: +5/+35°C; medium-temperature: −10/+35°C; low-temperature: −35/+35°C.
2. Data apply to units with refrigerant-cooled oil coolers. The source specifies a suction subcooling value of 5°C.
200 Series single-stage compressor unit specifications
Item Unit 200 Series
Refrigerant type R717
Model 200S 200M 200L
Theoretical displacement m³/h 810 1020 1210
Capacity control range Stepless adjustment: 10–100%
Cooling capacity High-temperature conditions Kw 976 1233 1487
Medium-temperature conditions Kw 539 681 821
Low-temperature conditions / with economizer Kw 166/195 210/247 255/298
Motor High-temperature conditions Kw 185 220 250
Medium-temperature conditions Kw 185 220 250
Low-temperature conditions / with economizer Kw 132 185 185/220
Electrical supply 380V/50HZ/3N
Rated speed r/min 2960
Direction of rotation Clockwise (viewed from the motor shaft end)
Refrigeration oil Grade 46#
Standard GB/T 16630, Refrigeration Oils
Charge quantity Kg 350 450 450
Notes:
1. High-temperature conditions: +5/+35°C; medium-temperature: −10/+35°C; low-temperature: −35/+35°C.
2. Data apply to units with refrigerant-cooled oil coolers. The source specifies a suction subcooling value of 5°C.
250 Series single-stage compressor unit specifications
Item Unit 250 Series
Refrigerant type R717
Model 250S 250M 250L
Theoretical displacement m³/h 1580 1980 2360
Capacity control range Stepless adjustment: 10–100%
Cooling capacity High-temperature conditions Kw 1933 2527 2897
Medium-temperature conditions Kw 1069 1343 1604
Low-temperature conditions / with economizer Kw 334/393 420/493 504/590
Motor High-temperature conditions Kw 315 450* 500*
Medium-temperature conditions Kw 315 400* 450*
Low-temperature conditions / with economizer Kw 250/280 315* 400*
Electrical supply 380V/50HZ/3N 10KV/50HZ/3N
Rated speed r/min 2960
Direction of rotation Clockwise (viewed from the motor shaft end)
Refrigeration oil Grade 46#
Standard GB/T 16630, Refrigeration Oils
Charge quantity Kg 750 750 800
Notes:
1. High-temperature conditions: +5/+35°C; medium-temperature: −10/+35°C; low-temperature: −35/+35°C.
2. Data apply to units with refrigerant-cooled oil coolers. The source specifies a suction subcooling value of 5°C.
START YOUR PROJECT

Taking freshness further.

Discuss your refrigeration project ↗
WhatsApp